JX
JX purification
| Availability: | |
|---|---|
The JX Automatic Chemical Dosing System is mainly composed of a dosing tank (chemical storage tank), metering pump (dosing pump), automatic control system, and connecting pipelines. Except for some dosing pipelines, sampling pipelines and dosing concentration monitoring instruments, the equipment is generally installed centrally in one dosing room. The automatic dosing system integrates the dosing tank, metering pump and automatic control system into one unit, mounted on a single base.
1) Fully Automatic Dosing Equipment
Adopts time-program control. First, the automatic dosing cycle, dosing amount, dosing time and dosing frequency are set according to the system operation requirements. During subsequent system operation, the metering pump automatically starts dosing when the dosing cycle arrives, and stops when the set dosing time is reached. At the blowdown cycle, the metering pump stops dosing; after the set blowdown time, the metering pump restarts to supplement the chemicals lost through blowdown, maintaining the system's chemical concentration at a normal level.
2) Intelligent Dosing Equipment
Adopts sensor signals to control the operation of the dosing pump. This control method requires monitoring instruments such as pH meters and conductivity meters, along with corresponding sensors. First, the limit values for control parameters (pH value or conductivity value) are set according to the system operation requirements. If the pH value is lower or higher than the set value during system operation, the dosing unit starts working: low pH indicates excessively strong acidity and corrosion tendency, while high pH indicates excessively strong alkalinity and scaling tendency. The monitoring instrument feeds this signal back to the control system, which then outputs instructions to the specified metering pump to open the dosing system for pH adjustment. The metering pump stops after the pH returns to normal. If the conductivity is higher than the set value, it indicates excessive salt content in the system with corrosion and scaling tendency. The monitoring instrument feeds this signal back to the control system, which outputs instructions to the blowdown solenoid valve to open drainage. After the conductivity returns to normal, the solenoid valve closes. Then the metering pump opens to dose chemicals, supplementing the chemicals lost through blowdown, maintaining the system's chemical concentration at a normal level, and stops dosing when the set time is reached.
Specifications :
Parameter | Specification |
|---|---|
System Pressure | 0.2 – 1.0 MPa |
Power Supply | 220V / 50Hz |
Ambient Temperature | 5 – 45℃ |
Relative Humidity | ≤ 85% |
Dosing Tank | Equipped with dosing tank |
Dosing Pump Type | Mechanical Diaphragm Metering Pump |
Control Mode | Time-based / Automatic |
Frame Material | Carbon Steel / Stainless Steel 304 |
Advantages :
Two Control Modes Available: Time-programmed automatic dosing for standard applications, and sensor-based intelligent dosing (pH/conductivity) for precise water quality control.
Integrated Skid Design: Dosing tank, metering pump and automatic control system are integrated on one base, with compact structure and easy installation.
Automatic Concentration Maintenance: The system automatically supplements chemicals lost through blowdown, maintaining the chemical concentration at a normal level continuously.
Centralized Installation: All equipment is installed in one dosing room, with convenient operation and maintenance.
Applications :
The JX automatic dosing system is widely used in:
Water treatment plants (coagulation, flocculation, disinfection)
Boiler water treatment (anti-scalant, pH adjustment, oxygen scavenger dosing)
Cooling water systems (corrosion inhibitor, biocide dosing)
Wastewater treatment plants (PAC/PAM dosing, neutralization)
RO / UF membrane systems (antiscalant dosing)
Food & beverage, pharmaceutical, chemical industries